90
Reference Manual
00809-0100-4021, Rev JA
HART Commissioning
April 2017
HART Commissioning
Configure Rosemount X-well technology with AMS Device Manager
Perform the following procedure:
1. Right click on the device and select Configure.
2. In the menu tree, select Manual Setup.
3. Select the Sensor tab.
4. Select either Rosemount X-well Process or Rosemount X-well Custom.
5. Select desired configurations via Basic Configuration and select Send.
Figure 3-7. Manual Setup - Sensor Screen
3.9 Device output configuration
Device output configuration contains PV range values, alarm and saturation, HART output, and LCD
display options.;PV range values
Field Communicator
The PV URV and PV LRV commands, found in the PV Range Values menu screen, allow the user to set the
transmitter’s lower and upper range values using limits of expected readings. See Table A-1 on page 183
for unit and range setting limits. The range of expected readings is defined by the Lower Range Value
(LRV) and Upper Range Value (URV). The transmitter range values may be reset as often as necessary to
reflect changing process conditions. From the PV Range Values screen select 1 PV LRV to change the
lower range value and 2 PV URV to change the upper range value.
HART 5 Fast Keys
2, 2, 5, 5
HART 7 Fast Keys
2, 2, 5, 5