10
Reference Manual
00809-0100-4021, Rev JA
Installation
April 2017
Installation
2.2.6 Software compatibility
Replacement transmitters may contain revised software that is not fully compatible with the existing
software. The latest device descriptors (DD) are available with new Field Communicators or they can be
loaded into existing communicators at any Emerson Service Center or via the Easy Upgrade process. For
more information on upgrading a Field Communicator, see Section 3: HART Commissioning.
To download new device drivers, visit Emerson.com/Rosemount/Device-Install-Kits.
2.3 Commissioning
The Rosemount 3144P Transmitter must be configured for certain basic variables to operate. In many
cases, these variables are pre-configured at the factory. Configuration may be required if the variables
need to be changed.
Commissioning consists of testing the transmitter and verifying transmitter configuration data.
transmitters can be commissioned either before or after installation. Commissioning the transmitter on
the bench before installation using a Field Communicator or AMS
Device Manager ensures that all
transmitter components are in working order.
For more information on using the Field Communicator with the transmitter, see Section 3: HART
Commissioning. For more information on using the Rosemount 3144 with F
OUNDATION Fieldbus, see
Section 4: Foundation Fieldbus Configuration.
Figure 2-2. Installation Flowchart
2.3.1 Setting the loop to manual
Set the process application loop to manual when sending or requesting data that would disrupt the loop
or change the output of the transmitter. The Field Communicator or AMS Device Manager will prompt to
set the loop to manual, when necessary. Acknowledging the prompt does not set the loop to manual, it
is only a reminder. Setting the loop to manual is a separate operation.
No
Yes
No
Yes
Bench
Calibration?
BASIC SETUP
Refer to Section
5: Operation and
Maintenance
Set Units
Set Range
Values - HART
Set Sensor Types
Set Number of
Wires
VERIFY
Simulate Sensor
Input
FIELD INSTALL
Set Jumpers or
Switches
Mount the
Transmit ter
Power the
Transmit ter
Check for Process
Leaks
Wire the
Transmitter
START HERE
Done
Within
Specifications?
Set Damping

Table of Contents