A. Remote sensor housing
B. Transmitter
C. Sensor
D. Shield ground parts
Ground the transmitter: option 3
Procedure
1. Ground sensor wiring shield at the sensor, if possible.
2. Ensure the sensor wiring and signal wiring shields are electrically
isolated from the transmitter housing and other grounded fixtures.
3. Ground signal wiring shield at the power supply end.
A. Sensor
B. Transmitter
C. Shield ground points
Quick Start Guide March 2021
16 Rosemount 3144P