3 Verify configuration
The Rosemount 3144P Transmitter communicates using a Field
Communicator (communication requires a loop resistance between 250 and
1100 ohms) or AMS Device Manager.
Do not operate when power is below 12 Vdc at the transmitter terminal.
Refer to the Rosemount 3144P Transmitter Reference Manual and Field
Communicator Reference Manual.
3.1 Update the Field Communicator software
To fully communicate with the Rosemount 3144P Transmitter, you need the
latest Field Communicator Field Device Revision Dev v5 or v7, DD v1 or
greater. Transmitters equipped with Rosemount X-well Technology require
DD revision 3144P Dev. 7 Rev. 1 or greater to view this functionality.
The Device Descriptors are available with new communicators at
Emerson.com/Rosemount, or you can download them into existing
communicators at any Emerson Service Center.
The device descriptors are as follows:
Device in HART 5 mode: Device v5 DDv1
Device in HART 7 mode: Device v7 DDv1
Complete the following steps to determine if you need to upgrade your
device. Refer to Figure 3-1.
Quick Start Guide March 2021
6 Rosemount 3144P