4.8.3 Wiring diagram
Figure 4-15: Wiring Diagram for FOUNDATION Fieldbus
A. Handheld communicator
B. Approved IS barrier (for Intrinsically Safe installations only)
C. FOUNDATION Fieldbus modem
D. Power supply
Note
Rosemount 5300 Level Transmitters with flameproof/explosion-proof output have a built-
in barrier; no external barrier needed.
Note
For intrinsically safe installations, make sure the instruments in the loop are installed in
accordance with intrinsically safe field wiring practices.
Note
For explosion-proof/flameproof installations, make sure the transmitter is grounded to the
internal ground terminal inside the terminal compartment in accordance with national
and local electrical codes.
4.9 Connect wiring and power up
Procedure
1. Make sure the power supply is switched off.
2. Remove the terminal block cover.
Reference Manual Electrical installation
00809-0100-4530 April 2019
Reference Manual 107