c) If using pipe, chamber or nozzle, then select the Pipe/Chamber/Nozzle Inner
Diameter.
d) If using nozzle, then enter the Nozzle Height.
9. In the Environment window, specify tank environment.
a) Select the Measurement Mode. See Measurement mode for further
information.
b) Enter the Product Dielectric Range/Upper Product Dielectric Constant. See
Product dielectric range and Upper product dielectric constant for further
information.
10. In the Volume window, select the Volume Calculation Method. Choose from:
• None (if volume calculation is not desired at all)
• Strapping table (if the actual tank does not match any of the available options
for pre-defined tanks, or if higher calculation accuracy is desired)
• Ideal spherical tank
• Ideal vertical cylinder
• Ideal horizontal cylinder
• Ideal vertical bullet
• Ideal horizontal bullet