11. If an ideal tank shape is selected, then enter the Diameter and Length (not for
spherical tanks). See Standard tank shapes for further information.
12. If Strapping Table is selected, starting at the bottom of the tank, for each new
point, enter the total volume up to the specified level value. See Strapping table for
further information.
13. (Optional) Enter the Volume Offset value. See Volume offset for further
information.
14. (HART only) In the Analog Out 1 window, configure the analog output.
a) In the Output Source (PV) list, select the desired transmitter variable to use for
the analog output. See Output source/primary variable for further
information.
b) Specify the analog output range by setting the Lower Range Value (4 mA)
and the Upper Range Value (20 mA) to the desired values. See Upper/lower
range value for further information.
c) In the Alarm Mode AOut 1 list, select the Alarm Mode you want to use for your
analog out channel. See Alarm mode for further information.
15. In the Finish Configuration Wizard window, select Finish and continue with the next
step in the guided setup.