Reset trim near zone using Rosemount Radar Master
To reset the Trim Near Zone function to factory setttings:
Procedure
1. Select Setup Advanced.
2. Select the Near Zone tab.
3. Select Trim Near Zone.
4. Select Reset near zone trimming to factory settings, and then select OK.
Reset trim near zone using AMS or a handheld communicator
To reset the Trim Near Zone function to factory setttings:
Procedure
1. HART
®
: Select Overview Echo Tuning.
FOUNDATION
Fieldbus: Configure Manual Setup Avanced.
2. Select Near Zone Reset near zone trimming to factory settings and follow the
instructions.
Changing the hold off distance/upper null zone
The Hold Off Distance/Upper Null Zone (UNZ) defines how close to the Upper Reference
Point a level value is accepted. You can extend the Hold Off Distance/UNZ to block out
disturbing echoes close to the tank top, see Figure 7-29.
Reference Manual Service and troubleshooting
00809-0100-4530 April 2019
Reference Manual 227