Output variables
Table A-8: Output Variables
Variable 5301 5302 5303 PV, SV, TV, QV
Level ✓ ✓ ✓ ✓
Distance to Level (Ullage) ✓ ✓ ✓ ✓
Level Rate ✓ ✓ ✓ ✓
Signal Strength ✓ ✓ ✓ ✓
Volume ✓ ✓ ✓ ✓
Internal Temperature ✓ ✓ ✓ ✓
Interface Level (✓)
(1)
✓ N/A ✓
Interface Distance (✓)
(1)
✓ N/A ✓
Interface Level Rate (✓)
(1)
✓ N/A ✓
Interface Signal Strength (✓)
(1)
✓ N/A ✓
Upper Layer Thickness (✓)
(1)
✓ N/A ✓
Lower Volume (✓)
(1)
✓ N/A ✓
Upper Volume (✓)
(1)
✓ N/A ✓
Signal Quality ✓ ✓ ✓ (✓)
(2)
Surface/Noise Margin ✓ ✓ ✓ (✓)
(2)
Vapor DC ✓ N/A N/A (✓)
(2)
Analog Output
Current
(3)(4)
✓ ✓ ✓ N/A
% of Range
(4)
✓ ✓ ✓ N/A
(1) Interface measurement only for fully submerged probe, see Figure A-16.
(2) Not available as primary variable.
(3) Not available for FOUNDATION
™
Fieldbus, Modbus
®
Signal Output, or for HART
®
units in fixed
current mode.
(4) LCD display variable only.
Damping
0-60 s (2 s, default value)
A.2.7
Diagnostics
General
Transmitter diagnostics with alerts include hardware and software errors, electronics
temperature, probe missing, and invalid measurement and configuration error
diagnostics. In addition to this, echo curve and variable logging including signal strength
facilitate easy on-line troubleshooting.
Reference Manual Specifications and reference data
00809-0100-4530 April 2019
Reference Manual 287