Figure D-2: The Probe End Projection Function
The product Level is given by the relation between Probe End displacement Δ, the
Dielectric Constant of the product, and distance D.
A. Surface pulse is missing due to low product reflectivity
B. Probe End pulse
C. Actual Probe End position
D. Distance
E. Apparent Probe End position
Note
It is important that the Probe Length and product Dielectric Constant are given with high
accuracy.
D.3.1
Setup the probe end projection
Prerequisites
Note
Assure that the Mounting Type, Probe Type, and Probe Length have been assigned correct
values before configuring the Probe End Projection.
Note
This function is only available for liquid/solid product level measurement modes (i.e. not
available for interface or fully submerged interface measurement modes) and a well
Advanced configuration Reference Manual
April 2019 00809-0100-4530
400 Rosemount 5300 Level Transmitter