• Probe types: Single lead or Coaxial/Large coaxial (standard/HP/C).
Note
When the thin layer detection is disabled, the minimum detectable upper product
thickness is increased, typically 5.1 in. (13 cm).
Procedure
1. HART
®
: Select Configure → Manual Setup → Level Setup → Environment.
FOUNDATION
™
Fieldbus: Select Configure → Manual Setup → Environment.
2. Select Thin Layer Detection.
The current state of the thin layer detection is presented.
3. Set thin layer detection to desired state.
4. Select Send and follow the instructions.
Advanced configuration Reference Manual
April 2019 00809-0100-4530
420 Rosemount 5300 Level Transmitter