Table H-1: Advanced Configuration Transducer Block Parameters (continued)
Parameter Index Number Description
XD_ERROR 11 A transducer block alarm subcode.
COLLECTION_DIRECTORY 12
AMPLITUDE_THRESHOLD_
CURVE
13 ATC: filters out weak disturbance echoes and noise.
SIMULATION_MODE 14 Simulation of measurement values.
SET_CONSTANT_THRESH
OLD
15 A constant amplitude threshold can be used to filter out noise.
RADAR_LEVEL_RANGE 16
RADAR_LEVEL_SIG-
NAL_STRENGTH_RANGE
17
RADAR_VOLUME_RANGE 18
ENV_PRESENTATION 19
PROBE_END_THRESH 20 This threshold is used to locate the probe end echo. The probe end
echo is used by the device to know when the tank is empty, but is
sometimes also useful when no surface echo can be found.
REFERENCE_THRESH 21 This threshold is used to locate the reference echo.
INTERFACE_THRESH 22 This threshold is used to block out disturbing echoes and noise when
locating the interface echo.
FULL_TANK_THRESH_OFF
SET
23 By adding an offset to the Reference Threshold it is possible for the
device to determine when the tank is full. If the reference echo
amplitude is between the Reference Threshold and the Full Tank
Threshold then the tank is considered full.
PEP_PRODUCT_DC 24 Enter the product dielectric constant for the product in the tank.
AUTO_CONF_MEAS_FUNC 25
ECHO_TIME_OUT 26 Change this parameter to define the time in seconds before the device
should start to search for a surface echo after it has been lost.
CLOSE_DIST 27 This parameter defines a window centered at the current surface
position where new surface echo candidates can be selected. The size
of the window is +/-Close Distance. Echoes outside this window will
not be considered as surface echoes.
USED_PROBE_END_THRES
H
28 Probe End Threshold currently used in the device.
USED_REFERENCE_THRES
H
29 Reference Threshold currently used in the device.
USED_INTERFACE_THRESH 30 Interface Threshold currently used in the device.
USED_TANK_PRESENTATI
ON
31
USED_ECHO_TIME_OUT 32 Echo Timeout currently used in the device.
USED_CLOSE_DIST 33 Close Distance currently used in the device.
Advanced Configuration Transducer Block Reference Manual
April 2019 00809-0100-4530
442 Rosemount 5300 Level Transmitter