Table I-1: Resource Transducer Block Parameters (continued)
Parameter Index number Description
RESTART 16 Allows a manual restart to be initiated. Several degrees of restart are
possible. They are the following:
1 Run – nominal state when not restarting
2 Restart resource – not used
3 Restart with defaults – set parameters to default values. See
START_WITH_DEFAULTS below for which parameters are set.
4 Restart processor – does a warm start of CPU.
RS_STATE 07 State of the function block application state machine.
SAVE_CONFIG_BLOCKS 62 Number of EEPROM blocks that have been modified since last burn.
This value will count down to zero when the configuration is saved.
SAVE_CONFIG_NOW 61 Allows the user to optionally save all non-volatile information
immediately.
SECURITY_IO 65 Status of security switch.
SELF_TEST 59 Instructs resource block to perform self-test. Tests are device specific.
SET_FSTATE 29 Allows the FAIL_SAFE condition to be manually initiated by selecting
Set.
SHED_RCAS 26 Time duration at which to give up on computer writes to function
block RCas locations. Shed from RCas shall never happen when
SHED_ROUT = 0
SHED_ROUT 27 Time duration at which to give up on computer writes to function
block ROut locations. Shed from ROut shall never happen when
SHED_ROUT = 0
SIMULATE_IO 64 Status of simulate switch.
SIMULATE_STATE 66 The state of the simulate switch:
0 = Uninitialized
1 = Switch off, simulation not allowed
2 = Switch on, simulation not allowed (need to cycle jumper/
switch)
3 = Switch on, simulation allowed
ST_REV 01 The revision level of the static data associated with the function block.
START_WITH_DEFAULTS 63 0 = Uninitialized
1 = do not power-up with NV defaults
2 = power-up with default node address
3 = power-up with default pd_tag and node address
4 = power-up with default data for the entire communications
stack (no application data)
STRATEGY 03 The strategy field can be used to identify grouping of blocks.
SUMMARY_STATUS 56 An enumerated value of repair analysis.
Reference Manual Resource Transducer Block