Table I-3: RB.RECOMMENDED_ACTION (continued)
Alarm type Failed/Maint/Advise Active
event
Recommended action text
string
Failed Level / Interface
Measurement Failure
Analyze echo curve for
reason and check device
configuration.
Check device physical
installation (for instance
probe contamination).
Load default database to
the device and
reconfigure it.
If error persists, it might
indicate a hardware
error. Replace the
transmitter head.
Volume / Temperature
Measurement Failure
If Level Measurement
Failure is active, clear
that alert first.
Check volume
configuration.
Load default database to
the device and
reconfigure it.
Check ambient
temperature at
installation site.
If error persists, it might
indicate a hardware
error. Replace the
transmitter head.
Electronics Failure -
Transducer Block
Replace transmitter head.
Probe Missing Check that the probe is
properly connected.
Input / Output Failure Replace the transmitter.
Non-Volatile Memory Failure Load default database to
the device to clear the
error.
Download a device
configuration.
If error persists, it may
indicate a faulty memory
chip. Replace the
transmitter head.
Reference Manual Resource Transducer Block