Figure 3-32: Rigid Twin Lead Probe Secured to the Tank Wall
$
A. Ø 0.3 in. (8 mm)
Coaxial probe
The coaxial probe can be secured to the tank wall by fixtures fastened to the tank wall.
Fixtures are customer supplied. Make sure the probe can move freely due to thermal
expansion without getting stuck in the fixture.
Figure 3-33: Coaxial Probe Secured to the Tank Wall
$
A. Coaxial: Ø 1.1 in. (28 mm), Large coaxial: Ø 1.7 in. (42 mm)
The coaxial probe can be guided by a tube welded on the tank bottom. Tubes are
customer supplied. Make sure that the probe can move freely in order to handle thermal
expansion. The measurement accuracy will be reduced close to the tube opening.
Reference Manual Mechanical installation
00809-0100-4530 April 2019
Reference Manual 91