3.4 Perform comprehensive, fully remote proof-
test (B)
3.4.1 Perform comprehensive, fully remote proof-test (B) with
Rosemount Radar Master
Prerequisites
WARNING
During the proof-test, the transmitter will not output measurement values corresponding
to the product surface level. Ensure systems and people relying on measurement values
from the transmitter are made aware of the changed conditions. Failure to do so could
result in death, serious injury and/or property damage.
Procedure
1. Bypass the safety function and take appropriate action to avoid a false trip.
2. Disable write protection in device (if enabled).
a) Select Tools → Lock/Unlock Configuration Area.
b) Enter password to unlock.
3. Using Loop Test, enter current value (mA) representing high alarm current. Verify
that analog output current is correct using the reference meter.
a) Select Setup → Output → Analog Out 1 and click Loop test.
b) Enter current value representing high alarm current.
c) Click Start to output current.
d) Verify that analog output current is correct.
e) Click Stop to end loop test.
4. Using Loop Test, enter current value (mA) representing low alarm current. Verify
that analog output current is correct using the reference meter.
a) Select Setup → Output → Analog Out 1 and click Loop test.
b) Enter current value representing low alarm current.
c) Click Start to output current.
d) Verify that analog output current is correct.
e) Click Stop to end loop test.
5. Enable write protection.
a) Select Tools → Lock/Unlock Configuration Area.
b) Enter password to lock.
Safety Manual
Proof tests
00809-1900-4530 September 2020
Rosemount 5300:SIS Level Transmitter 23