4. Using Loop Test, enter current value (mA) representing low alarm current. Verify
that analog output current is correct using the reference meter.
a) Select Setup → Output → Analog Out 1 and click Loop test.
b) Enter current value representing low alarm current.
c) Click Start to output current.
d) Verify that analog output current is correct.
e) Click Stop to end loop test.
5. Enable write protection.
a) Select Tools → Lock/Unlock Configuration Area.
b) Enter password to lock.
6. Perform High Level Supervision test.
a) Select Setup → Advanced.
b) Select the Level Supervision tab.
c) Select Start/Stop Test Mode.
d) Verify that the output from the device corresponds to the alarm limit in the
host system.
e) End test mode by clicking Start/Stop Test Mode.
The device will automatically exit the test mode after 30 minutes [default].
7. Remove the bypass and otherwise restore normal operation.
For more information on the High Level Supervision, refer to Rosemount 5300 Level
Transmitter High Level Supervision Manual Supplement.
For troubleshooting the transmitter, see Reference Manual.
3.6.2
Perform comprehensive, fully remote proof-test using
reference reflector (High Level Supervision) (D) with
AMS Device Manager and handheld communicator
Prerequisites
WARNING
During the proof-test, the transmitter will not output measurement values corresponding
to the product surface level. Ensure systems and people relying on measurement values
from the transmitter are made aware of the changed conditions. Failure to do so could
result in death, serious injury and/or property damage.
Prerequisites
This proof-test can only be performed on devices with Verification reflectors (high level
supervision) option code HL1, HL2 or HL3.
Safety Manual
Proof tests
00809-1900-4530 September 2020
Rosemount 5300:SIS Level Transmitter 31