4 Operating constraints
4.1 Specifications
The Rosemount 5300 Level Transmitter must be operated according to the functional and
performance specifications provided in the Rosemount 5300 Level Transmitter Product
Data Sheet.
4.1.1 Measuring range
Up to 164 ft (50 m)
4.1.2
Failure rate data
The FMEDA report includes failure rate data, assessment details, and assumptions
regarding failure rate analysis.
4.1.3
Safety deviation
2.0 %
(1)
4.1.4
Transmitter response time
At least below 8 seconds for specific configurations
Higher Transmitter response time is allowed for other user-selectable configurations, for
example damping, level rate etc. See Reference Manual for more information.
4.1.5
Diagnostic test interval
< 90 minutes
4.1.6
Start-up time
< 40 s
(2)
4.1.7
Useful lifetime
50 years
based on worst case component wear-out mechanisms
not based on wear-out of process wetted materials
(1)
The safety deviation of the Rosemount 5300 Level Transmitter safety-certified option is ±2% of full span (± 0.32 mA).
(2) The start-up time is extended with five additional minutes for option code BR5 at temperatures below -40 °F (-40 °C). Refer
to Rosemount 5300 Cold Temperature Option Code BR5 Manual Supplement.
Safety Manual Operating constraints
00809-1900-4530 September 2020
Rosemount 5300:SIS Level Transmitter 41