EasyManua.ls Logo

Emerson ROSEMOUNT 5300 - Page 118

Emerson ROSEMOUNT 5300
324 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Reference Manual
00809-0100-4530, Rev BA
July 2009
Rosemount 5300 Series
5-46
7. Configure Tri-Loop Channel 1:
a. Assign variable: Tri-Loop HART command [1,2,2,1,1].
Make sure that the SV, TV, and QV match the configuration of the
5300 transmitter.
b. Assign units: Tri-Loop HART command [1,2,2,1,2]. Make sure that
the same units are used as for the 5300 transmitter.
c. Set the Upper Range Value and the Lower Range Value: Tri-Loop
HART command [1,2,2,1,3-4].
d. Enable the channel. Tri-Loop HART command [1,2,2,1,5].
8. (Optional) Repeat steps a-d for Channels 2 and 3.
9. Connect wires to Tri-Loop Burst Input.
10. Enter the desired tag, descriptor, and message information:
Tri-Loop HART command [1,2,3].
11. (Optional) If necessary, perform an analog output trim for Channel 1 (and
Channel 2 and 3 if they are used).
Tri-Loop HART command [1,1,4].
Figure 5-18. Tri-Loop wiring.
See the reference manual for the Model 333 HART Tri-Loop HART-to-Analog
Signal Converter for further information on how to install and configure the
Tri-Loop.
To turn off the Burst Mode
To turn off the Burst Mode, use one of the following options:
The RRM program
The Rosemount Burst Mode Switch software
A 375 Field Communicator
The AMS software
Each Tri-Loop
Channel
receives power
from Control
Room
Channel 1 must
be powered for
the Tri-Loop to
operate
Device receives
power from
Control Room
HART Burst Command 3/
Analog Output
Intrinsically Safe Barrier
DIN Rail Mounted
HART Tri-Loop
Control Room
QV
TV
SV
PV

Table of Contents

Other manuals for Emerson ROSEMOUNT 5300

Related product manuals