Reference Manual
00809-0100-4530, Rev BA
July 2009
A-7
Rosemount 5300 Series
EN:
316L SST according to EN 1092-1 Table 18, material group 13E0.
Standard: Max. 302 °F/580 psig
(150 °C/40 Bar).
HP/HTHP/C: Up to PN 320.
Alloy C-276 according to EN 1092-1 table 18 material group 12E0.
HP/HTHP: Up to PN320.
Fisher & Masoneilan:
According to ANSI B16.5 Table 2-2.3.
Standard: Max. 302 °F/580 psig
(150 °C/40 Bar).
HP/HTHP/C: 32 °F/1199 psig (20 °C/82.7 Bar).
Up to Class 600, Table 2.3.
JIS:
According to JIS B2220 Table 2.3
Standard: 10K/20K/150C.
HP/C: 10K/20K/200C.
HTHP: 10K/20K/400C
For Alloy C-276 HTHP/HP probes with flange plate design is available up to
Class 600/PN 63.
Ambient Temperature When the Rosemount 5300 is installed in high or low temperature
applications, it is important that the maximum/minimum ambient temperature
is considered. Nozzle insulation for the HTHP version should not exceed 4 in.
(10 cm).
The diagram below shows the ambient temperature vs. process temperature:
Figure A-5. Ambient
temperature vs. process
temperature.
NOTE!
The maximum ambient temperature also depends on hazardous locations
certfications.
-320 (-196)
-40 (-40)
-40 (-40)
-17 (-27)
Process
Temperature °F (°C)
Ambient Temperature °F (°C)