Rosemount 5300 Series
F-2
Channel Definitions Each input has an assigned channel which can be linked to the AI block. The
channels for the Rosemount 5300 Series are the following:
Table F-1. Channel
Assignments
PARAMETERS AND
DESCRIPTIONS
Table F-2. Level Transducer
Block Parameters and
Descriptions.
Channel Name
Channel
Number
Process variable
Level 1 CHANNEL_RADAR_LEVEL
Ullage 2 CHANNEL_RADAR_ULLAGE
Level Rate 3 CHANNEL_RADAR_LEVELRATE
Signal Strength 4 CHANNEL_RADAR_SIGNAL_STRENGTH
Volume 5 CHANNEL_RADAR_VOLUME
Internal Temperature 6 CHANNEL_RADAR_INTERNAL_TEMPERATURE
Upper Product Volume 7 CHANNEL_UPPER_PRODUCT_VOLUME
Lower Product Volume 8 CHANNEL_LOWER_ PRODUCT_VOLUME
Interface Distance 9 CHANNEL_INTERFACE_ DISTANCE
Upper Product Thickness 10 CHANNEL_UPPER_ PRODUCT_THICKNESS
Interface Level 11 CHANNEL_INTERFACE_LEVEL
Interface Level Rate 12 CHANNEL_INTERFACE_ LEVELRATE
Interface Signal Strength 13 CHANNEL_INTERFACE_ SIGNALSTRENGTH
Signal Quality 14 CHANNEL_SIGNAL_QUALITY
Surface/Noise Margin 15 CHANNEL_ SURFACE_NOISE_MARGIN
Vapor DC 16 CHANNEL_VAPOR_DC
Parameter Index Number Description
ST_REV 1 The revision level of the static data associated with the
function block. The revision value increments each time a
static parameter value in the block is changed.
TAG_DESC 2 The user description of the intended application of the block.
STRATEGY 3 The strategy field can be used to identify grouping of blocks.
This data is not checked or processed by the block.
ALERT_KEY 4 The identification number of the plant unit. This information
may be used in the host for sorting alarms, etc.
MODE_BLK 5 The actual, target, permitted, and normal modes of the block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
BLOCK_ERR 6 This parameter reflects the error status associated with the
hardware or software components associated with a block. It
is a bit string, so that multiple errors may be shown.
UPDATE_EVT 7 This alert is generated by any change to the static data.