EasyManua.ls Logo

Emerson Rosemount 5400 Series - Overview; Register Access Transducer Block Parameters; F.1 Overview

Emerson Rosemount 5400 Series
314 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
265
Reference Manual
00809-0100-4026, Rev HA
Appendix F: Register transducer block
November 2014
Register Transducer Block
Appendix F Register Transducer Block
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 265
F.1 Over view
The Register Transducer Block allows access to Database registers and Input registers of the
Rosemount 5400 transmitter. This makes it possible to read a selected set of registers directly
by accessing the memory location.
The Register Transducer Block is only available with advanced service.
F.1.1 Register access transducer block parameters
Table F-1. Register Access Transducer Block Parameters
Since this Register Transducer Block allows access to most registers in the transmitter,
which includes the registers set by the Methods and Configuration screens, in the Level
Transducer Block (see Appendix E: Level Transducer Block) it should be handled with care
and ONLY to be changed by trained and certified service personnel, or as guided by
Emerson Process Management, Rosemount Business Unit support personnel.
Parameter
Index
number
Default value Description
ST_REV 1
The revision level of the static data associated with the
function block. The revision value increments each time a
static parameter value in the block is changed.
TAG_DESC 2
The user description of the intended application of the
block.
STRATEGY 3 0
The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the block.
ALERT_KEY 4 0
The identification number of the plant unit. This
information may be used in the host for sorting alarms,
etc.
MODE_BLK 5
0x08(Auto)
0x08(Auto)
0x88(Auto | OOS)
0x08(Auto)
The actual, target, permitted, and normal modes of the
block.
Target: The mode to “go to”
Actual: The mode the “block is currently in”
Permitted: Allowed modes that target may take on
Normal: Most common mode for target
BLOCK_ERR 6
This parameter reflects the error status associated with
the hardware or software components associated with a
block. It is a bit string, so that multiple errors may be
shown.

Table of Contents