Section 4: Electrical Installation
November 2014
Electrical Installation
4.9.2 Non-intrinsically safe power supply
With non-intrinsically safe power supply in Non-hazardous installations or Explo-
sion-proof/Flameproof installations, wire the transmitter as shown in Figure 4-12.
Rosemount 5400 Series Transmitters with Explosion-proof/Flameproof Output have a built-in
barrier; no external barrier needed.
Note
Make sure that the power supply is off when connecting the transmitter.
Figure 4-12. Wiring for Non-Intrinsically Safe Power Supply (FOUNDATION fieldbus)
Note
For explosion-proof/flameproof installations make sure that the transmitter is grounded to the
IS ground terminal inside the terminal compartment in accordance with national and local
electrical codes.
Rosemount 5400 Series
radar transmitter
Field communicator
Fieldbus
modem
PC
Power
supply