170
Reference Manual
00809-0100-4026, Rev KC
Service and Troubleshooting
October 2018
Service and Troubleshooting
Threshold settings
To adjust the amplitude thresholds:
1. Select HART command [2, 5, 2].
The different echo curve options appear on the display:
2. Select option 1 Measure and Learn to create an ATC, see ATC” on page 110 for more information.
Select option 2 Set Threshold to specify a constant Surface Threshold.
3. Select the SAVE button to store the new settings in the transmitter database.