Figure B-1. Installation Drawing Ex n Rosemount 5400 Series
The copyright/ownership of this document is
and will remain ours. The document must not
be used without our authorization or brought
to the knowledge of a third party.
NON
-HAZARDOUS LOCATION HAZARDOUS LOCATION
HART:
42.4 VDC,
23 mA
FOUNDATION FIELDBUS:
32 VDC, 21
mA
Note 1
nA
Ui: 42.4 V
Ii: 23
mA
Pi:
1 W
Li: Negligible
Uo: 42.4 V Ci: 7.25 nF
ic Io: 23 mA Note 1
Po:
1 W
Lo > 0
Co > 7.25 nF
Notes:
1 Connect supply wires to the appropriate terminals as indicated on the terminal block label
and in the installation documents.
SPECIFIC CONDITIONS FOR SAFE USE (X):
1 The intrinsically safe circuits do not withstand the 500V AC test as specified in
IEC 60079-11 clause 6.4.13.
2 The antennas for type 5400, are non-conducting and the area of the non-conducting parts exceeds the
maximum permissible areas for Group IIC and according to EN/ IEC 60079-0: .2012/2011 clause 7.4:
20 cm
2
/ 80 cm
2
for EPL Gc. Therefore, when the antenna is used in a potentially explosive atmosphere,
appropriate measures must be taken to prevent electrostatic charge.
Input parameter
s for Non-sparking