threading the transmitter mounting screws into the universal head
mounting holes.
6. Mount the transmitter-sensor assembly into the thermowell. Seal
adapter threads with silicone tape.
7. Install conduit for field wiring to the conduit entry of the universal
head. Seal conduit threads with PTFE tape.
8. Pull the field wiring leads through the conduit into the universal
head. Attach the sensor and power leads to the transmitter.
Avoid contact with other terminals.
9. Install and tighten the universal head cover.
Enclosure covers must be fully engaged to meet explosion-proof
requirements.
Example
A. Threaded thermowell
B. Standard extension
C. Threaded style sensor
D. Universal head (transmitter and LCD inside)
E. Conduit entry