September 2016
10
Quick Start Guide
4.0 Set jumpers and switches
Adjust jumpers to desired settings.
4.1 HART
If alarm and security jumpers are not installed, the flowmeter will operate
normally with the default alarm condition alarm high and the security off.
Figure 8. HART Jumpers and LCD Display
4.2 Power supply
The dc power supply should provide power with less than two percent ripple. The
total resistance load is the sum of the resistance of the signal leads and the load
resistance of the controller, indicator, and related pieces. Note that the resistance
of intrinsic safety barriers, if used, must be included.
Figure 9. Load Limitation
A. Rloop in ohms
B. Power supply voltage
Maximum Loop Resistance = 41.7 (Power Supply Voltage - 10.8)
The Field Communicator requires a minimum loop resistance of 250 ohms
ALARM
HI
LO
ON
OFF
SECURITY
1500
1250
1000
750
500
250
0
10.8 16.8 22.8 28.8 34.8 42
B
A