Quick Start Guide
3. When the equipment is installed, particular precautions must be taken to ensure taking
into account the effect of process fluid temperature, that the ambient temperature of
the electrical housing of the equipment meets the marked protection type
temperature range.
Type ‘n’ certification
EN 60079-0: 2012 +A11: 2013
EN 60079-11: 2012
EN 60079-15: 2010
N1 Certification No. Baseefa12ATEX0180X
ATEX Marking: II 3 G
Ex nA ic IIC T5 Gc (-40 °C Ta +70 °C)
Maximum Working Voltage = 42 Vdc
Special Conditions for Safe Use (X):
1. When fitted with 90V transient suppressors, the equipment is not capable of passing
the 500V isolation test. This must be taken into account upon installation.
2. When the equipment is installed, particular precautions must be taken to ensure,
taking into account the effect of process fluid temperature, that the ambient
temperature of the electrical housing of the equipment meets the marked protection
type temperature range.
Flameproof certification
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-11: 2012
EN 60079-26: 2007
E1 Certification No. DEKRA12ATEX0189X
Integral Transmitter marked:
ATEX Marking: II 1/2 G
Ex d [ia] IIC T6 Ga/Gb
Remote Transmitter marked:
ATEX Marking: II 2(1) G
Ex d [ia Ga] IIC T6 Gb
Remote Sensor marked:
ATEX Marking: II 1 G
Ex ia IIC T6 Ga
Ambient temperature range: -50 °C Ta 70 °C
Maximum Working Voltage = 42 Vdc
Transmitter Um = 250V
Remote mounted sensor: in type of protection Ex ia IIC, only to be connected to the
associated Model 8600D Vortex Flow meter electronics.
The maximum allowable length of the interconnecting cable is 152 m (500-ft.)
Special Conditions for Safe Use (X):
1. For information regarding the dimensions of the flameproof joints the manufacturer
shall be contacted.
2. The Flowmeter shall be provided with special fasteners of property class A2-70 or
A4-70.