Reference Manual
00809-0300-4750, Rev CA
Advanced Configuration Functionality
March 2016
Advanced Configuration Functionality
5.2.2 Pulse output
Under this function the pulse output of the Rosemount 8750W can be configured.
Grounding/Wiring
Fault
(1)
Detailed Setup, Output
Config, Analog, AO
Diag Alarm,
Ground/Wiring
1, 4, 2, 1, 9, 3 Drive to an alarm state when
grounding or wiring fault is
detected.
High Process
Noise
(1)
Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Process
Noise
1, 4, 2, 1, 9, 4 Drive to an alarm state when
the transmitter detects high
levels of process noise.
Electronics Tem-
perature Out of
Range
(1)
Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Elect Temp
1, 4, 2, 1, 9, 5 Drive to an alarm state when
the temperature of the elec-
tronics exceeds allowable lim-
its
Electrode Coating
Limit 2
(1)(2)
Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Elec Coat-
ing
1, 4, 2, 1, 9, 6 Drive to an alarm state when
electrode coating reaches a
point where it impacts the
flow measurement
Totalizer Limit 1 Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Total Limit
1, 4, 2, 1, 9, 7 Drive to an alarm state when
the totalizer value exceeds the
parameters set in the total-
izer limit configuration (see
page 5-x for more details on
this functionality)
Flow Limit 1 Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Flow Limit
1
1, 4, 2, 1, 9, 8 Drive to an alarm state when
the flow rate exceeds the
parameters set in the flow
limit 1 configuration (see
page 5-x for more details on
this functionality)
Flow Limit 2 Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Flow Limit
2
1, 4, 2, 1, 9, 9 Drive to an alarm state when
the flow rate exceeds the
parameters set in the flow
limit 2 configuration (see
page 5-x for more details on
this functionality)
Continuous Meter
Verification
(1)(2)
Detailed Setup, Output
Config, Analog, AO
Diag Alarm, Cont Meter
Ver
1, 4, 2, 1, 9,
--
(3)
Drive to an alarm state when
the continuous meter verifica-
tion diagnostic detects a fail-
ure of one of the tests
1. See Section 6 for more details on each of the diagnostics.
2. Only available on the Field Mount Transmitter.
3. To access these features, you must scroll to this option in the HART Field Communicator.
LOI menu path
Field Mount: Detailed Setup, Output Config, Pulse
Wall Mount: N/A
Traditional Fast Keys
1, 4, 2, 2
Device dashboard
2, 2, 2, 2
Table 5-3. Analog Alarm Diagnostic Options
Diagnostic LOI menu path Fast Keys Description