6
Reference Manual
00809-0300-4750, Rev BA
Quick Installation and Start-Up
March 2016
Quick Installation and Start-Up
Be sure to identify any additional options and configurations that apply to the installation.
Keep a list of these options for consideration during the installation and configuration
procedures.
2.5.3 Mechanical considerations
The mounting site for the Rosemount 8750W should provide enough room for secure
mounting, easy access to conduit entries, full opening of the transmitter covers, and easy
readability of the LOI screen if equipped.
For remote mount transmitter installations, a mounting bracket is provided for use on a
2-in. pipe or a flat surface (see Figure 2-1 for field mount and Figure 2-3 for wall mount).
Note
If the transmitter is mounted separately from the sensor, it may not be subject to limitations
that might apply to the sensor.
Rotate integral mount transmitter housing or remote
junction box
The transmitter housing can be rotated on the sensor in 90° increments by removing the
four mounting screws on the bottom of the housing. Sensor lead wires should be
disconnected from the electronics before rotating the housing. Do not rotate the housing
more than 180° in any one direction. Prior to tightening, be sure the mating surfaces are
clean, the O-ring is seated in the groove, and there is no gap between the housing and the
sensor.