8.2 Certifications
Factory Mutual (FM)
Ordinary Location Certification for FM Approvals
As standard, the transmitter and flowtube have been examined and tested to determine
that the design meets basic electrical, mechanical, and fire protection requirements by FM
Approvals, a nationally recognized testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
Rosemount 8750W Magnetic Flowtube and Transmitter
Z5 All Flowtubes and Integral or Remote Mount Transmitters
(Transmitter mount codes T or R)
Non-Incendive for Class I, Division 2, Groups ABCD: T4 Dust-Ignition Proof for
Class II/III, Division 1, Groups EFG: T5 -29 °C ≤ T
a
≤ 60 °C
Enclosure Type 4X, IP66/68 (IP68 flowtube only with Remote mount transmitter)
Install per drawing 8750W-1052.
Special Condition for Safe Use (X):
1. Flowtube to be used only in a non-flammable process.
Rosemount 8750W Magnetic Flowtube and Transmitter
Z5 All Flowtubes and Wall Mount Transmitter (Transmitter mount code W)
Non-Incendive for Class I, Division 2, Groups ABCD: T4 Dust-Ignition Proof for
Class II/III, Division 1, Groups EFG: T4-29 °C ≤ T
a
≤ 40 °C
Enclosure Type 4X, IP66/68 (IP68 flowtube only)
Install per drawing 8750W-1052.
Special Condition for Safe Use (X):
1. Flowtube to be used only in a non-flammable process.
CSA
Ordinary Location Certification for FM Approvals
As standard, the transmitter and flowtube have been examined and tested to determine
that the design meets basic electrical, mechanical, and fire protection requirements by FM
Approvals, a nationally recognized testing laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
Rosemount 8750W Magnetic Flowtube and Transmitter
Z6 Non-Incendive for Class I, Division 2, Groups ABCD: T4
Dust-Ignition Proof for Class II/III, Division 1, Groups EFG: T4 -29 °C ≤ T
a
≤ 60 °C
(Transmitter mount codes T or R)
-29 °C ≤ T
a
≤ 40 °C (Transmitter mount code W)
Enclosure Type 4X, IP66/68/69K
(1)
Install per drawing 8750W-1052.
Special Condition for Safe Use (X):
1. Flowtube to be used only in a non-flammable process.