Figure 3-4: Sensor orientation
A. Flow direction
3.2.5
Electrode orientation
The electrodes in the sensor are properly oriented when the two measurement electrodes
are in the 3 and 9 o’clock positions or within 45 degrees from the horizontal, as shown on
the left side of Figure 3-5. Avoid any mounting orientation that positions the top of the
sensor at 90 degrees from the vertical position as shown on the right of Figure 3-5.
Figure 3-5: Electrode orientation
A
B
A. Correct orientation
B. Incorrect orientation
Sensor Installation Reference Manual
November 2019 00809-0100-8782
16 Rosemount
®
8782 Slurry Magnetic Flow Meter Transmitter with HART Protocol