8 Advanced Configuration
Functionality
8.1 Introduction
This section contains information for advanced configuration parameters.
The software configuration settings for the transmitter can be accessed through a HART
®
-
based communicator, Local Operator Interface (LOI), or through a control system. Before
operating the transmitter in an actual installation, you should review all of the factory set
configuration data to ensure that they reflect the current application.
8.2 Configure outputs
LOI menu path Detailed Setup → Output Config
The configure outputs functionality is used to configure advanced features that control
the pulse, auxiliary, and totalizer outputs of the transmitter.
8.2.1
Analog output
LOI menu path Detailed Setup → Output Config → Analog
The analog output function is used to configure all of the features of the 4-20 mA output.
Upper range value
LOI menu path
Detailed Setup → Output Config → Analog → PV URV
The upper range value (URV) sets the 20 mA point for the analog output. This value is
typically set to full-scale flow. The units that appear will be the same as those selected
under the units parameter. The URV may be set between –39.3 ft/s to 39.3 ft/s (–12 m/s
to 12 m/s) or the equivalent range based on the selected flow units. There must be at least
1 ft/s (0.3 m/s) span or equivalent between the URV and LRV.
Note
If entering a negative number, the minus sign must be entered in the furthest left position
on the LOI.
Reference Manual Advanced Configuration Functionality
00809-0100-8782 November 2019
Reference Manual 69