WARNING
Explosion hazards. Failure to follow these instructions could cause an explosion,
resulting in death or serious injury.
• If installed in explosive atmospheres (hazardous areas, classified areas, or an “Ex”
environment), it must be assured that the device certification and installation
techniques are suitable for that particular environment.
• Do not remove transmitter covers in explosive atmospheres when the circuit is live.
Both transmitter covers must be fully engaged to meet explosion-proof
requirements.
• Do not disconnect equipment when a flammable or combustible atmosphere is
present.
• Before connecting a HART-based communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
• Follow national, local, and plant standards to properly earth ground the transmitter
and sensor. The earth ground must be separate from the process reference ground.
• Flow meters ordered with non-standard paint options or non-metallic labels may be
subject to electrostatic discharge. To avoid electrostatic charge build-up, do not rub
the flow meter with a dry cloth or clean with solvents.
WARNING
Electrical hazards. Failure to follow these instructions could cause damaging and unsafe
discharge of electricity, resulting in death or serious injury.
• Follow national, local, and plant standards to properly earth ground the transmitter
and sensor. The earth ground must be separate from the process reference ground.
• Disconnect power before servicing circuits.
• Allow ten minutes for charge to dissipate prior to removing electronics
compartment cover. The electronics may store energy in this period immediately
after power is removed.
• Avoid contact with leads and terminals. High voltage that may be present on leads
could cause electrical shock.
• Flow meters ordered with non-standard paint options or non-metallic labels may be
subject to electrostatic discharge. To avoid electrostatic charge build-up, do not rub
the flow meter with a dry cloth or clean with solvents.
NOTICE
Damage hazards
Failure to follow these instructions could result in damage or destruction of equipment.
• The sensor liner is vulnerable to handling damage. Never place anything through the
sensor for the purpose of lifting or gaining leverage. Liner damage may render the
sensor inoperable.
• Metallic or spiral-wound gaskets should not be used as they will damage the liner face
of the sensor. If spiral wound or metallic gaskets are required for the application, lining
Reference Manual Hazard messages