26
Reference Manual
00809-0100-4772, Rev FA
Installation
March 2016
Installation
3.4.5 High-temperature installations
Install the meter body so the electronics are positioned to the side of the pipe or below the
pipe, as shown in Figure 3-6. Insulation may be required around the pipe to maintain a
temperature below 185 °F (85 °C).
Figure 3-6. Examples of High-Temperature Installations
A. The meter body installed with the electronics to the side of the pipe (preferred orientation).
B. The meter body installed with the electronics below the pipe (acceptable orientation).
Important
When insulation is used, install it around the pipe and meter body only. The support tube
bracket and electronic transmitter should not be insulated. See Figure 3-7.
Figure 3-7. Insulation
A. Do not insulate within the RED area.
B. 1 in. (25 mm) minimum
A
B
A
B