Transducer Block
March 2016
Transducer Block
ELEC_TEMP_RANGE 108 This parameter reports the measurement range of the electronics
temperature sensor (MTA model).
Upper sensor range = 90 °C
Lower sensor range = -55 °C
ELECTRON_TEMP 107 In an MTA model transmitter the electronics temperature is available.
This parameter will report the current temperature of the electronics in
engineering units configured in ELECTRON_TEMP_UNITS
ELECTRON_TEMP_UNITS 93 In an MTA model transmitter the electronics temperature is available.
This parameter is used to configure the engineering units of the
electronics temperature.
ELECTRONICS_STATUS 70 This parameter represents the transducer block electronics status. See
4.2.2: Diagnostics.
FACTORY_INFO_FLOAT 80 For factory use only.
FACTORY_INFO_INDEX 79 For factory use only.
FACTORY_INFO_U16 82 For factory use only.
FACTORY_INFO_U32 83 For factory use only.
FACTORY_INFO_U8 81 For factory use only.
FILTER_AUTO_ADJUST
LOW_PASS_CODE
42 Selecting a fluid density close to the process density will adjust the
Trigger Level, Low Flow Cutoff, and Low Pass Filter to values that will work
well for most applications.
FILTER_RESTORE 43 This parameter will restore the Low Flow Cutoff, Low Pass Filter, and
Trigger Level to default configurations base on the mass of air for gas
process fluids or the mass of water for liquid process fluids.
1 = Normal state, 2 = Restore filters to defaults.
FIXED_PROC_DENSITY 50 The configured density of the process fluid is used to calculate flow when
mass units are selected.
FIXED_PROC_DENSITY_UNITS 51 The engineering units of PROCESS_DENSITY:
1097 = kilograms per cubic meter
1107 = pounds per cubic foot
FIXED_PROC_TEMP_UNITS 53 The engineering units of process temperature:
1001 = °C
1002 = °F
FIXED_PROC_TEMPERATURE 52 Process temperature is the configured temperature of the process fluid,
in units of °C or °F. This parameter is used to compensate the K-factor for
meter body expansion due to temperature. It is also used to calculate the
PROCESS_DENSITY_RATIO.
FLANGE_TYPE 36 Flange type specifies the wafer or the flange construction material (i.e.
ASME 150, ASME 300, ASME 600, PN64, JIS 10K, etc.). Flange type is
used as an input to the compensated K-factor calculation.
INSTALLATION_EFFECTS 32 An adjustment to the Compensated K-Factor to account for less than
ideal upstream piping effects.
K_FACTOR 31 The K-factor is the meter body calibration number. Units are reflected in
K_FACTOR_UNITS.
K_FACTOR_UNITS 34 K-factor units are the engineering units to be applied to the K_FACTOR
and COMPD_K_FACTOR.
0 = Pulses per gallon
LFC_IN_ENG_UNITS 45 This read-only parameter will indicate Low Flow Cutoff in currently
configured engineering units.
Table 4-1. Transducer Block Parameters