72
Reference Manual
00809-0100-4772, Rev FA
Resource Block
March 2016
Resource Block
5.2.3 Alarm detection
A block alarm will be generated whenever the BLOCK_ERR has an error bit set. The types of
block error for the resource block are defined above (see Table 5-2).
A write alarm is generated whenever the WRITE_LOCK parameter is cleared. The priority of
the write alarm is set in the following parameter:
WRITE_PRI
Alarms are grouped into five levels of priority as shown in Table 5-3.
5.2.4 Status handling
There are no status parameters associated with the resource block.
5.2.5 VCR
The number of configurable VCRs is 19. The parameter is not contained or viewable within
the resource block, but it does apply to all blocks.
5.2.6 Troubleshooting
Refer to Table 5-4 to troubleshoot any problems that you encounter.
Table 5-3. Alarm Priority
Priority
number
Priority description
0 The priority of an alarm condition changes to 0 after the condition that caused the
alarm is corrected.
1 An alarm condition with a priority of 1 is recognized by the system, but is not
reported to the operator.
2 An alarm condition with a priority of 2 is reported to the operator, but does not
require operator attention (such as diagnostics and system alerts).
3–7 Alarm conditions of priority 3 to 7 are advisory alarms of increasing priority.
8–15 Alarm conditions of priority 8 to 15 are critical alarms of increasing priority.
Table 5-4. Troubleshooting
Symptom Possible causes Corrective action
Mode will not
leave OOS.
Target mode not set Set target mode to something other than OOS.
Memory failure BLOCK_ERR will show the lost NV Data or Lost
Static Data bit set. Restart the device by setting
RESTART to processor. If the block error does not
clear, call the factory.
Block alarms
will not work.
Features FEATURES_SEL does not have Alerts enabled.
Enable the Alerts bit.
Notification LIM_NOTIFY is not high enough. Set equal to
MAX_NOTIFY.
Status options STATUS_OPTS has Propagate Fault Forward bit set,
which should be cleared to cause an alarm to occur.