4.4 Set fixed current 4-20 values
4-20mA is factory calibrated with controlled and certified equipment; there is no need for
additional calibration. This process allows rounding of multimeter values to 4mA and
20mA fixed values.
For different equipment used at the customer site over ±0.05mA, the 4-20mA output can
be fixed to match the reading indicated on the customer's multimeter. The reading can be
adjusted within ±0.05mA.
Procedure
1. Select the 4 mA radio button
2. Click Set fixed current.
3. Enter multimeter reading.
4. Click the Apply button.
5. Repeat steps Step 3 and Step 4 until you enter value within 4mA ±0.5.
Important
It is essential to enter the final value and click Apply.
6. Select the 20 mA radio button.
7. Click Set fixed current.
8. Enter multimeter reading.
9. Click the Apply button.
10. Repeat steps Step 8 and Step 9 until you enter value within 20mA ±0.5.
Important
It is essential to enter the final value and click Apply.
11. Click the Burn button to save the changes.
Maintenance
Reference Manual
June 2021 00809-1500-4975
28 Emerson.com