12
Reference Manual
00809-0200-4975, Rev A
HART Menu Structure
June 2017
HART Menu Structure
5.4 Device setup menu
Figure 5-4. Device Setup Menu
Table 5-3. Device Setup Menu Commands
1 Manufacturer Rosemount, Inc. Read
2 Model 975 Read
3 Dev ID Device unique identification number Read
4
Config. Changed
Counter
The number of Device Configuration changes since the
manufacture.
Read
5 Enable Alarm Latch
Enables the alarm relay to remain energized after exiting
the Alarm Mode.
Read
6
Activate ACC relay
on Warning
Activates ACC relay during Warning status.
R/W
7 Enable Auto BIT Activates alarm after successful self-test. R/W
8
Activate ACC relay
on Successful BIT
Activates ACC Relay after successful self-test.
R/W
9
Activate Alarm on
Successful BIT
Activates Alarm after successful self test.
R/W
10 ACC as E.O.L Accessory Relay is activated at Power on Continuously. R/W
11 Sensitivity Detectors Sensitivity setting R/W
12 Alarm Delay Defines the delay between Fire Detection and Alarm. R/W
13 Heater Mode Select a Heater Mode: Auto, On, or Off. R/W
14 Heater on Temp.
This option is active in Heater Auto mode. It allows
setting the temperature at which the optics heater begins
operating.
R/W
15 Poll Address The address used by the host to identify a field device. R/W
16 Loop Current Mode Select a Current Mode: Fixed or Not Fixed. R/W