10 Product certifications
10.1 Rosemount 3051SMV/3051SFx Product Certifications
Rev 2.0
European Directive Information
A copy of the EU Declaration of Conformity can be found at the end of the
Quick Start Guide. The most recent revision of the EU Declaration of
Conformity can be found at Emerson.com/Rosemount.
Ordinary Location Certification
As standard, the transmitter has been examined and tested to determine that
the design meets the basic electrical, mechanical, and fire protection
requirements by a nationally recognized test laboratory (NRTL) as accredited
by the Federal Occupational Safety and Health Administration (OSHA).
Installing Equipment in North America
The US National Electrical Code
®
(NEC) and the Canadian Electrical Code (CEC)
permit the use of Division marked equipment in Zones and Zone marked
equipment in Divisions. The markings must be suitable for the area
classification, gas, and temperature class. This information is clearly defined in
the respective codes.
10.1.1 USA
E5 US Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate
FM16US0089X
Standards
FM Class 3600 – 2011, FM Class 3615 – 2006, FM Class 3616 –
2011, 3810 – 2005,ANSI/NEMA 250 – 2003
Markings
XP CL I, DIV 1, GP B, C, D; T5; DIP CL II, DIV 1,GP E, F, G; CL III;
T5(–50 °C ≤ T
a
≤ +85 °C); Factory Sealed; Type 4X
I5 US Intrinsically Safe (IS) and Nonincendive (NI)
Certificate
FM16US0233
Standards
FM Class 3600 – 2011, FM Class 3610 – 2007, FM Class 3611 –
2004, FM Class 3810 – 2005, NEMA 250 – 1991
Markings
IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; Class
1, Zone 0 AEx ia IIC T4; NI CL 1, DIV 2, GP A, B, C, D; T4(–50 °C≤ T
a
≤ +70 °C) when connected per Rosemount drawing 03151-1206;
Type 4X
Quick Start Guide October 2018
32 Rosemount 3051SMV