Standards
CAN/CSA C22.2 No. 0-10, CSA Std C22.2 No. 25-1966, CSA Std
C22.2 No. 30-M1986, CSA C22.2 No. 94.2-07, CSA Std C22.2
No. 213-M1987, CAN/CSA C22.2 60079-11:14, CAN/CSA-C22.2
No. 61010-1-12, ANSI/ISA 12.27.01-2003, CSA Std C22.2 No.
60529:05 (R2010)
Markings
FISCO Intrinsically Safe Class I, Division 1; Groups A, B, C, D;
suitable for Class I, Zone 0; T3C, Ta = 70 °C; when installed per
Rosemount drawing 03151-1207; Type 4X
10.1.3 Europe
E1 ATEX Flameproof
Certificate
KEMA 00ATEX2143X
Standards
EN 60079-0:2012+A11:2013, EN 60079-1: 2014, EN
60079-26:2015
Markings
II 1/2 G Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ T
a
≤ +70 °C), T5/
T4(–60 °C ≤ T
a
≤ +80 °C)
Temperature class Process temperature
T6 –60 °C to +70 °C
T5 –60 °C to +80 °C
T4 –60 °C to +120 °C
Special Conditions for Safe Use (X):
1. This device contains a thin wall diaphragm less than 1 mm thickness
that forms a boundary between Category 1 (process connection) and
Category 2 (all other parts of the equipment). The model code and
datasheet are to be consulted for details of the diaphragm material.
Installation, maintenance, and use shall take into account the
environmental conditions to which the diaphragm will be subjected.
The manufacturer's instructions for installation and maintenance shall
be followed in detail to assure safety during its expected lifetime.
2. Flameproof joints are not intended for repair.
3. Non-standard paint options may cause risk from electrostatic
discharge. Avoid installations that could cause electrostatic build-up
on painted surfaces, and only clean the painted surfaces with a damp
cloth. If paint is ordered through a special option code, contact the
manufacturer for more information.
4. Appropriate cable, glands, and plugs need to be suitable for a
temperature of 5 °C greater than maximum specified temperature for
location where installed.
Quick Start Guide October 2018
34 Rosemount 3051SMV