RSTi-OM User Manual Section 6
GFK-3212A Jun 2021
IO-Link Master Port Configuration
52
An IO-Link device is operating on the port that has received valid PDI
data.
An IO-Link device is operating on the port that has not received valid
PDI data.
One of the following conditions exists:
A valid IO-Link device is not connected to the port.
A digital input or output device is connected to the port but the
configured Port Mode is not correct.
Port is functioning correctly in IO-Link mode but has not received
valid PDI data.
This may also display during a data storage upload or download.
The port is attempting initialization.
One of the following conditions exists:
The Port Mode configuration is set to Reset.
The Port Mode configuration is set to DigitalIn or DigitalOut.
Hardware failure (IO-Link LED also flashes red) because there is Data
Storage on this port, which does not reflect the attached device.
Hardware failure (IO-Link LED also flashes red) because Device
Validation is configured for this port and the wrong device is
attached.
Hardware failure (IO-Link LED also flashes red) because the size of the
configuration on the device does not match the size of the
configuration stored on the port.
Temporary state after a device is disconnected and before the port is
re-initialized.
Temporary status displayed when the device:
It is starting up after connection or power-up.
Uploading or downloading automatic data storage.
Note: If a digital input or output device is connected to an IO-Link port, there is no valid data until the
port is set to the correct Port Mode.
4. Review the Device IO-Link Version.
• If the field is blank, it is not a valid IO-Link device, which could mean that it is a digital device and
the port has not been configured for digital input or digital output.
• The field displays the Device IO-Link version.
5. Optionally, review the following to see if you need to change the Configured Minimum Cycle
Time:
• Actual Cycle Time
• Device Minimum Cycle Time
• Configured Minimum Cycle Time