RSTi-OM User Manual Section 6
GFK-3212A Jun 2021
IO-Link Master Port Configuration
63
Modbus/TCP Settings Page
Clear Event Code After Hold
Time
Default: True
If enabled, the IO-Link Master clears any event code reported in the PDI
data block after the Event Active Hold Time.
Values are:
True (enable check box) = clear event code after hold time
False = do not clear event code after the hold time
Active Event Hold Time
Default: 1000 ms
If Clear Event Code After Hold Time is enabled, the time period an
event code is reported in the PDI block before it is cleared.
Valid range: 1-65535
Valid Units are:
ms (milliseconds)
sec (seconds)
min (minutes)
hours
days
Event Hold Time Units
Valid Units:
ms (milliseconds)
sec (seconds)
min (minutes)
hours
days
Clear Event Hold Time
Default: 500 ms
Once an event code has been cleared, the time an event code stays
cleared in the PDI block before another event code can be reported.
Valid range: 1-65535
Valid Units:
ms (milliseconds)
sec (seconds)
min (minutes)
hours
days
Event Clear Time Units
Valid Units:
ms (milliseconds)
sec (seconds)
min (minutes)
hours
days
Include Digital Output(s) in
PDO Data Block
Default: False
If enabled, the IO-Link Master expects the digital output settings to
be included in the PDO data block.
False The digital pin setting(s) are not included in the PDO data
block
True (enable check box) The digital pin setting(s) are included in the
PDO data block
Transfer Mode Settings
Slave Mode Device ID
Default: 1
The Modbus Device ID was used to access this IO-Link port.
Range: 1-247
PDI Receive Mode(s)
Default: Slave
Determines which PDI Receive (To PLC) Modes are enabled. The
selectable modes are:
Slave
Master
PDO Transmit Mode
Default: Slave
Selectable Modes are:
Disabled
Slave
Master
Modbus Master PLC IP
Address
The IP address of the Modbus slave.
Modbus Master PLC Device ID
(1-247)
(Default: 1)
The Modbus Device ID was used to access the slave.
Modbus Master PLC PDI Data
Address (base 1)
(1-65535)
(Default: 1)
The address of the slave’s PDI (determined by the slave).
Modbus Master PLC Max
Update Rate (0-10000)
(Default: 0)
How often to write PDI to the slave.
Modbus Master PLC PDO Data
Address (base 1) (1-65535)
(Default:1)
The address of the slave’s PDO (determined by the slave).
Modbus Master PLC Poll Rate
(40- 65535)
(Default: 40)
How often to read PDO from the slave.