Menu 11 − Miscellaneous
Mode: Openloop
Parameter 11.018 Status Mode Parameter 1
Short description Defines the parameter displayed on the upper row of the keypad when in status mode
Mode Openloop
Minimum 0.000 Maximum 30.999
Default 2.001 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW, PT, BU
StatusModeParameter1 (11.018) and StatusModeParameter2 (11.019) defines which parameters are displayed in Status mode.
The values can be alternated by pressing the Escape key if the drive status is RUN.
If one of the two Status parameter does not exist or is 0.000, only one Status parameter is displayed.
If the two Status parameters do not exist or are 0.000, the active parameter is displayed.
Parameter 11.019 Status Mode Parameter 2
Short description Defines the parameter displayed on the lower row of the keypad when in status mode
Mode Openloop
Minimum 0.000 Maximum 30.999
Default 4.020 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW, PT, BU
See StatusModeParameter1 (11.018).
Parameter 11.020 Reset Serial Communications
Short description Set to one to update communications set-up
Mode Openloop
Minimum 0 Maximum 1
Default Units
Type 1 Bit Volatile Update Rate Background read
Display Format Standard Decimal Places 0
Coding RW, ND, NC
When SerialAddress (11.023), SerialMode (11.024), SerialBaudRate (11.025), MinimumCommsTransmitDelay (11.026) or SilentPeriod (11.027)
are modified the changes do not have an immediate effect on the serial communications system. The new values are used after the next power-up or if
ResetSerialCommunications (11.020) is set to one. ResetSerialCommunications (11.020) is automatically cleared to zero after the communications
system is updated.
Parameter 11.021 Customer defined scaling
Short description Defines the scaling of 11.018 in status view
Mode Openloop
Minimum 0.000 Maximum 10.000
Default 1.000 Units
Type 16 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW
Customerdefinedscaling (11.021) defines the scaling applied to StatusModeParameter1 (11.018). The scaling is only applied in the Status mode.
Parameter 11.022 Active Parameter At Power-up
Short description Defines which parameter is displayed at power-up in view mode
Mode Openloop
Minimum 0.000 Maximum 0.095
Default 0.010 Units
Type 8 Bit User Save Update Rate Background read
Display Format Standard Decimal Places 3
Coding RW, PT, BU
ActiveParameterAtPower-up (11.022) defines which Menu 0 parameter is initially active at power-up in view mode. If ActiveParameterAtPower-up
(11.022) > 10 and UserSecurityStatus (11.044) is set to Level1 then Parameter 10 is set as the power up parameter.
See StatusModeParameter1 (11.018).
Unidrive M200 Parameter Reference Guide
Issue: 01.05.00.10
173