Unidrive M200-201 Quick Start Guide 35
Issue Number: 6
This parameter controls access via the drive keypad as follows:
Defines the reference when jog is enabled.
00.010 {11.044} User Security Status
RW Num ND NC PT US
OL
Ú
LEVEL.0 (0), ALL (1), r.only.0 (2),
r.only.A (3), Status (4), no.Acc (5)
Ö
LEVEL.0 (0)
RFC-A
Value Text Function
0 Menu 0 (LEVEL.0)
All writable parameters are available to be edited but only parameters in
Menu 0 are visible.
1 All Menus (ALL) All writable parameters are visible and available to be edited.
2
Read-only Menu 0
(r.only.0)
All parameters are read-only. Access is limited to Menu 0 parameters only.
3 Read-only (r.only.A) All parameters are read-only however all menus and parameters are visible.
4 Status Only (Status)
The keypad remains in status mode and no parameters can be viewed or
edited.
5 No Access (no.Acc)
The keypad remains in status mode and no parameters can be viewed or
edited. Drive parameters cannot be accessed via a comms/fieldbus interface
in the drive or any option module.
00.015 {01.005} Jog Reference
RW Num US
OL
Ú
0.00 to 300.00 Hz
Ö
1.50 Hz
RFC-A
Unidrive M200 201 Quick Start Guide English Iss6.book Page 35 Thursday, September 10, 2015 1:48 PM