Defines the event to trigger when a timeout occurs. Modbus Timeout Event Destination
(S.15.011) must specify an appropriate consumer (slot option) of the event.
Specifies the Modbus register addressing mode.
This parameter specifies an IP address for a priority connection.
Value Text Description
0 No event No event
1 Trigger Event Trigger module Event
2 Trigger Event 1 Trigger module Event 1
3 Trigger Event 2 Trigger module Event 2
4 Trigger Event 3 Trigger module Event 3
5 Trigger Event 4 Trigger module Event 4
This feature is not yet implemented.
S.15.013 Modbus Register Addressing Mode
Minimum 0 Maximum 1
Default 0 Units
Type 8 Bit User Save Update Rate
Module reset, Modbus
interface reset or Modbus
interface enable
Display Format None Decimal Places 0
Coding RW, TE, BU
Value Text Description
0 Standard (mm x 100) + ppp - mm<=162 and ppp<=99
1 Modified (mm x 256) + ppp - mm<=63 and ppp<=255
S.15.020 Priority Connection 1
Minimum
0
(Display: 0.0.0.0)
Maximum
4294967295
(Display: 255.255.255.255)
Default
0
(Display: 0.0.0.0)
Units
Type 32 Bit User Save Update Rate
Module reset, Modbus
interface reset or Modbus
interface enable
Display Format IP Address Decimal Places 0
Coding RW, BU