SI-Ethernet User Guide 91
Issue: 1
Safety
information
Introduction
Mechanical
installation
Electrical
installation
Getting started Parameters
Key features
and Protocols
PC Applications Security Diagnostics
Glossary of
terms
Index
Variable length output assembly object (instance 101) with consistency for up
to 20 parameters
User selectable RPI timeout action
Identity object (class 0x01)
Motor data object (class 0x28)
Control supervisor object (class 0x29)
AC/DC Drive object (class 0x2A)
Control Techniques objects (classes 0x64 to 0x69)
Explicit (non-cyclic) access to parameters
EtherNet/IP server port
The Ethernet interface uses the standard server port 44818 (0xAF12) for EtherNet/IP
communications, this is fixed and cannot be changed.
Parameter Update Rate
Parameters are exchanged over the network. The value exchanged over the network
must be exchanged with the drive or option parameter. The rate of data exchange differs
for drive and option destinations.
The diagram below depicts the update cycles used within the Ethernet interface. CIP
assembly mappings being exchanged with the drive will be updated at the background
task rate. This rate (Background cycles per second (S.09.008)) varies with the load on
the Ethernet interface; Easy Mode non-synchronized data exchange also takes place in
the background task.
Synchronous
Cyclic Links
Cyclic Links
Background
Task
500 µs
O
P
T
I
O
N
S
D
R
I
V
E
>=500 µs
Network
>=1 ms