92 SI-Ethernet User Guide
Issue: 1
This parameter is used to enable or disable EtherNet/IP slave functionality.
This parameter is used to perform a warm reset of the protocol interface. When set and
the protocol has reset, the parameter will be reset to zero (Off).
This parameter allows the protocol to be defaulted to factory settings. This includes all
of the protocol features, configuration, mappings and stored objects.
S.20.001 Enable EtherNet/IP
Minimum 0 Maximum 1
Default 1 Units
Type 1 Bit User Save Update Rate Background read
Display Format None Decimal Places 0
Coding RW, BU
If either Input Assembly Object Size (S.20.020) or Output Assembly Object Size
(S.20.021) is a non zero value then the available mappings will still be consumed even
if the Ethernet/IP functionality is disabled.
S.20.002 Reset
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate
Background read; written to
0 on initialization
Display Format Decimal Places 0
Coding RW, NC
S.20.003 Default
Minimum 0 Maximum 1
Default 0 Units
Type 1 Bit Volatile Update Rate
On module reset, protocol
interface reset or protocol
enable
Display Format None Decimal Places 0
Coding RW, NC
S.20.004 Configuration error
Minimum 0 Maximum 8
Default Units
Type 8 Bit Volatile Update Rate Background
Display Format None Decimal Places 0
Coding RO, TE, ND, NC, PT, BU