This parameter defines and shows the required input assembly object.
This parameter defines and shows the required output assembly object.
S.20.018 Active input assembly object
Minimum 0 Maximum 4
Default 0 Units
Type 8 Bit Volatile Update Rate
Module reset, EtherNet/IP
interface reset or EtherNet/
IP interface enable
Display Format None Decimal Places 0
Coding RO, TE, NC, PT, BU
Value Text Description
0 100-PrimaryI Primary input (100)
1 70-BscSpdCtrlI Basic speed control input (70)
2 71-ExtSpdCtrlI Extended speed control input (71)
3 72-SpdTqCtrlI Speed and torque control input (72)
4 73-ExtSpdTqCtrlI Extended speed and torque control input (73)
S.20.019 Active output assembly object
Minimum 0 Maximum 4
Default 0 Units
Type 8 Bit Volatile Update Rate
Module reset, EtherNet/IP
interface reset or EtherNet/
IP interface enable
Display Format None Decimal Places 0
Coding RO, TE, NC, PT, BU
Value Text Description
0 101-PrimaryO Primary output (101)
1 20-BscSpdCtrlO Basic speed control output (20)
2 21-ExtSpdCtrlO Extended speed control output (21)
3 22-SpdTqCtrlO Speed and torque control output (22)