Document Part # 026-4280 Rev 1 Page 11 of 33
©2022 Emerson Digital Cold Chain, Inc. This document may be photocopied for personal use.
Visit our website at www.climate.emerson.com for the latest technical documentation and updates.
The LSn and LAn parameter are used only to show the actual settings (read only). See Figure 9-2 for an example of configuration:
9.1.1. Daily Defrost From RTC: [EdF = rtC]
IdF Parameter: For safety reasons, force the value of Idf at +1 with respect to the interval between the two Ld parameters.
The IdF timer is restarted after defrost and at every power ON.
DEFROST START: At the time selected by the parameters Ld1 to Ld6 or Sd1 to Sd6.
DEFROST END: If the probes reach the dtE temperature or for maximum MdF time.
SAFETY and RtC or RtF ALARM: With clock alarm, the device will use the parameters IdF, dtE and MdF.
MULTIMASTER DEFROST: All the probes with real-time clock function:
Figure 9-2 - Configuration Example
CAUTION: Do not set [EdF = rtC] and [CPb = n].
Parameter Unit A (RTC) Unit B (RTC) Unit C (RTC)
Adr n N + 1 N + 2
EdF rtC (clock) rtC (clock) rtC (clock)
IdF 9 hours safety 9 hours safety 9 hours safety
MdF 45 minutes safety 45 minutes safety 45 minutes safety
dtE 12°C safety 12°C safety 12°C safety
Ld1 06:00 1° 06:00 1° 06:00 1°
Ld2 14:00 2° 14:00 2° 14:00 2°
Ld3 22:00 3° 22:00 3° 22:00 3°
Table 9-3 - Multi-master Defrost Example